ESIE05-07 The Functional Controller for DICN
Part 2 – Functional Description 2–97
3
2
4
5
1
3.13 Capacity Limitation
MS Option = yes
(network unit)
MS Option = no
(standalone unit)
Limitation Mode Equal for all units Dedicated to this unit only.
Changing Limitation
mode
When changed in one unit the
value is transferred to all units.
When changed in a unit the
value is NOT transferred to other
units
Activate limitation by
Schedule timer
Set schedule timer of the Master
unit (see remark).When a limita-
tion is activated it will be trans-
ferred to all units.
Set schedule timer of unit
Dedicated to this unit only.
Enable/disable limitation
By remote digital inputs
In the service menu of each unit,
you can select a changeable
Digital Input.
The limitation is dedicated to this
unit only.
Into the service menu of each
unit, you can select a changea-
ble Digital Input.
The limitation is dedicated to this
unit only.
Remark: schedule timer is only available on master unit.