Daikin EWAP460MBYN [260/452] Password function

Daikin EWAD240MBYNN [260/452] Password function
Functional Control for a Standalone Unit ESIE05-07
2–64 Part 2 – Functional Description
3
1
2
4
5
2.20 Password Function
Introduction A user password can be chosen, in the user password menu, to protect the user settings.
In the user settings menu it can be chosen whether a password is needed to change the setpoint.
In the service menu you can choose if a password is needed to reset safeties. This password can be
either the user password either the service password.
Overview of
possibilities
A user password is used to protect the user parameters. This password can be set in the user
password menu.
A service password is used to protect the service parameters; this password is factory set and cannot
be changed.
User password Service password
1234 (default) 1914 (fixed)
1. Setpoint menu (only if Setpoint password is
enabled in the user settings menu)
Yes Yes
2. User settings menu Yes Yes
3. Service menu No Yes
4. User password menu Yes Yes
Additionally: depending on the status of the "password needed to reset safety" parameter in the
service menu.
5. Possible to reset a safety in safety menu if
user password is required
Yes Yes
6. Possible to reset a safety in safety menu if
service password is required
No Yes
Possible to enter with
Menu
ESIE05-07.book Page 64 Wednesday, October 11, 2006 10:42 AM

Содержание