Functional Control for a Standalone Unit ESIE05-07
2–70 Part 2 – Functional Description
3
1
2
4
5
Possible settings (Service menu):
P Simulation setting:
P AI Setting:
P AO Setting:
P DIS. EEV Setting:
P STL Setting:
Simulation parameter Application
Simulation = NO actual unit
Simulation = YES simulation board is selected
Simulation parameter Application
AI = 0 actual unit = actual sensors are used on
the analog inputs
AI = 1 simulation board (all analog inputs use
potentiometers = NTC)
Simulation parameter Application
AO = 0 variable analog output from 0V to 10V
AO = 1 analog output with 2 possible outputs,
0V or 5V output
Simulation parameter Application
DIS. EEV = 0 actual unit with EEV driver
DIS. EEV = 1 If no EEV driver is connected to the
simulation board this parameter should
be put on 1. This will dissable the EEV
control on the controller.
Simulation parameter Application
STL = O actual unit, controller uses the feedback
from the compressor. The compressor
capacity is calculated based on the
feedback value
STL = 1 if no compressor control motor is con-
nected to the controller of the simulation
board, then this parameter should be
programmed on 1. Now the controller
will simulate the feedback resistance.
ESIE05-07.book Page 70 Wednesday, October 11, 2006 10:42 AM