ESIE05-07 Functional Control for a Standalone Unit
Part 2 – Functional Description 2–29
3
2
4
5
1
Example of Freeze-up with inlet check at reset.
The system has also the possibility to check the inlet water temperature before reset. If the setting is
put on "Y", then the system will look at the evaporator outlet water temperature as well as at the
evaporator inlet water temperature. If the setting is put on "N" then the system will only look to the
evaporator outlet water temperature.
When you use inlet check at reset not only the outlet water must rise above the MOW but also the
evaporator inlet water temperature must rise with 1.5°C step-length
Setting of MOW It is possible to change the MOW temperature (from -10 to 8°C) in the service menu if necessary.
e.g. for applications with glycol.
General overview The following table shows a general view of freeze-up temperatures in case of protection and
prevention.
Line N° Display Description Possibility Default
3 INL CHECK AT
RESET
Evaporator inlet water tempera-
ture check before reset
Y/N N
2
1
Outlet temp
Freeze-up setpoint
(2.5 C)
(MOW Default = 4 C)
2 (Default) times freeze-up in less than 60 min (Default)
Freeze-up disable
Freeze-up safety
Time
Automatic reset:
Inlet temp
^I
(more than 1.5 C)
Possible to reset by user:
Inlet temp
^I (more than 1.5 C)
Possible to reset
Minimum outlet
water (M.O.W.)
freeze-up protec-
tion setpoint
freezing-point of
the solution
Glycol percent-
age
Standard 4°C 2.5°C 0°C 0%
ZH -5°C -6.5°C -16°C 30%
ZL -10°C -11.5°C -22°C 40%
ESIE05-07.book Page 29 Wednesday, October 11, 2006 10:42 AM