Functional Control for a Standalone Unit ESIE05-07
2–54 Part 2 – Functional Description
3
1
2
4
5
Function
description of the
setpoint signal
Example setpoint signal 0-1V:
P If analog input AI3 has 1V then setpoint signal diff is equal to setpoint signal Diff max
P If analog input AI3 has 0V then setpoint signal diff is equal to 0.
P This value can also have a negative value (ex -10.0°C).
1V
0V
A
nalog signal
Setpoint Setpoint +
SetpSignalDiffMax
Setpoint
On readou
t
display
ESIE05-07.book Page 54 Wednesday, October 11, 2006 10:42 AM