Daikin RXY32MTL [112/346] Restart standby

Daikin RXY5MTLE [112/346] Restart standby
Si38-304 Special Control
Function 101
3.5 Restart Standby
* Actuators are based on RX(Y)16M.
Actuator Operation Remarks
Compressor OFF
Outdoor unit fan
Ta>30°C: STEP5
Ta30°C: OFF
Four way valve Holds ON
Main motorized valve (EV1) 0 pls
Subcooling motorized valve (EV2) 0 pls
Hot gas bypass valve (SVP)
OFF In the case of RX(Y)5M , this valve
turns ON.
Oil equalization valve (SVO)
ON In the case of slave units, this valve
turns OFF.
Receiver gas charging valve (SVL) OFF
Receiver gas discharging valve (SVG) OFF
Non-operating unit gas discharging
valve (SVSG)
OFF
Non-operating unit liquid pipe stop
valve (SVSL)
ON
Ending conditions 5 min.