Daikin RXY32MTL [99/346] Compressor pi control

Daikin RXY22MY1E [99/346] Compressor pi control
Basic Control Si38-304
88 Function
2.2 Compressor PI Control
Compressor PI Control
Carries out the compressor capacity PI control to maintain Te at constant during cooling
operation and Tc at constant during heating operation to ensure stable unit performance.
[Cooling operation]
[Heating operation]
Controls compressor capacity to adjust Te to
achieve target value (TeS).
Te : Low pressure equivalent saturation temperature
(°C)
Te setting TeS : Target Te value
(Varies depending on Te setting, operating
frequency, etc.)
LM (Normal)
(factory
setting)
H
369
Controls compressor capacity to adjust Tc to
achieve target value (TcS).
Tc : High pressure equivalent saturation temperature
(°C)
Tc setting TcS : Target Tc value
(Varies depending on Tc setting, operating
frequency, etc.)
LM (Normal)
(factory
setting)
H
43 46 49

Содержание

Скачать