Daikin RXY32MTL [271/346] Check no 12 check on pulse input of position signal of fan inverter pcb 1 disconnect the connector x2a while power supply off and operation off 2 is the voltage between pins no 4 and 5 on x2a approx 15 v after power supply is turned on 3 connect the connector x2a while power supply off and operation off 4 check below conditions when the fan motor is rotated one turn manually under the condition of operation off after power supply is turned on are the pulse approx 0 v and 5 v generated 4 times between no 1 and 5 on x2a are the pulse approx 0 v and 5 v generated 4 times between no 2 and 5 on x2a are the pulse approx 0 v and 5 v generated 4 times between no 3 and 5 on x2a

Daikin RXY18MY1 [271/346] Check no 12 check on pulse input of position signal of fan inverter pcb 1 disconnect the connector x2a while power supply off and operation off 2 is the voltage between pins no 4 and 5 on x2a approx 15 v after power supply is turned on 3 connect the connector x2a while power supply off and operation off 4 check below conditions when the fan motor is rotated one turn manually under the condition of operation off after power supply is turned on are the pulse approx 0 v and 5 v generated 4 times between no 1 and 5 on x2a are the pulse approx 0 v and 5 v generated 4 times between no 2 and 5 on x2a are the pulse approx 0 v and 5 v generated 4 times between no 3 and 5 on x2a
Troubleshooting (OP: Unified ON/OFF Controller) Si38-304
260 Troubleshooting
Check No. 12 Check on pulse input of position signal of fan inverter PCB
(1) Disconnect the connector X2A while power supply OFF and operation OFF.
(2) Is the voltage between pins No. 4 and 5 on X2A approx. 15 V after power supply is turned
on?
(3) Connect the connector X2A while power supply OFF and operation OFF.
(4) Check below conditions when the fan motor is rotated one turn manually under the condition
of operation OFF after power supply is turned ON.
Are the pulse (approx. 0 V and 5 V) generated 4 times between No. 1 and 5 on X2A?
Are the pulse (approx. 0 V and 5 V) generated 4 times between No. 2 and 5 on X2A?
Are the pulse (approx. 0 V and 5 V) generated 4 times between No. 3 and 5 on X2A?
The condition (2) dose not appear Faulty PCB Replacing the PCB
The conditions (4) do not appear Faulty hall IC Replacing fan motor of outdoor unit
5 Gray
4 Pink
3 Orange
2 Blue
1 Yellow
GND
Vcc (approx. 15 V)
Position signal W
Position signal V
Position signal U