Daikin RXY32MTL [237/346] Malfunction of transmission between indoor units

Daikin RXY40MY1 [237/346] Malfunction of transmission between indoor units
Troubleshooting by Indication on the Remote Controller Si38-304
226 Troubleshooting
2.42
U4
Malfunction of Transmission Between Indoor Units
Remote
Controller
Display
U4
Applicable
Models
All model of indoor unit
RX(Y)5~48M
Method of
Malfunction
Detection
Microcomputer checks if transmission between indoor and outdoor units is normal.
Malfunction
Decision
Conditions
When transmission is not carried out normally for a certain amount of time
Supposed
Causes
Indoor to outdoor,outdoor to outdoor transmission wiring F1, F2 disconnection, short circuit
or wrong wiring
Outdoor unit power supply is OFF
System address doesnt match
Defect of indoor unit PC board
Defect of outdoor unit PC board