Daikin RXY32MTL [186/346] The system operates for malfunction codes indicated in black squares however be sure to check and repair

Daikin RXY24MTLE [186/346] The system operates for malfunction codes indicated in black squares however be sure to check and repair
Si38-304 Troubleshooting by Remote Controller
Troubleshooting 175
Outdoor
Unit
LA 999Malfunction of power unit
LC 999Malfunction of transmission between inverter and
control PC board
217
P1 999Inverter over-ripple protection 219
P4 999Malfunction of inverter radiating fin temperature rise
sensor
220
System
U0 879Low pressure drop due to refrigerant shortage or
electronic expansion valve failure
221
U1 999Reverse phase / open phase 222
U2 999Power supply insufficient or instantaneous failure 223
U3 999Check operation is not conducted. 225
U4 999Malfunction of transmission between indoor and
outdoor units
226
U5 999Malfunction of transmission between remote
controller and indoor unit
228
U5 787Failure of remote controller PC board or setting
during control by remote controller
228
U7 999Malfunction of transmission between outdoor units 229
U8 997Malfunction of transmission between master and
slave remote controllers (malfunction of slave remote
controller)
231
U9 999Malfunction of transmission between indoor unit and
outdoor unit in the same system
232
UA 999Excessive number of indoor units etc. 234
UC 888Address duplication of central remote controller 235
UE 999Malfunction of transmission between central remote
controller and indoor unit
236
240
246
UF 999Refrigerant system not set, incompatible wiring /
piping
238
UH 999Malfunction of system, refrigerant system address
undefined
239
Centrali
zed
Control
and
Schedu
le
Timer
M1 8 or 79 9PC board defect 241
248
M8 8 or 79 9Malfunction of transmission between optional
controllers for centralized control
242
249
MA 8 or 79 9Improper combination of optional controllers for
centralized control
243
250
MC 8 or 79 9Address duplication, improper setting 245
252
Heat
Reclai
m
Ventilat
ion
64 879Indoor units air thermistor error
65 879Outside air thermistor error
68 879
6A 879Damper system alarm
6A 999Damper system + thermistor error
6F 879Malfunction of simple remote controller
6H 879Malfunction of door switch or connector
94 999Internal transmission error
Malfunction
code
Operation
lamp
Inspection
display
Unit No. Malfunction contents Page
Referred
The system operates for malfunction codes indicated in black squares, however, be sure to check and repair.