Daikin RXY32MTL [234/346] Power supply insufficient or instantaneous failure

Daikin RXY22MTL [234/346] Power supply insufficient or instantaneous failure
Si38-304 Troubleshooting by Indication on the Remote Controller
Troubleshooting 223
2.40
U2
Power Supply Insufficient or Instantaneous Failure
Remote
Controller
Display
U2
Applicable
Models
RX(Y)5~48M
Method of
Malfunction
Detection
Detection of voltage of main circuit capacitor built in the inverter and power supply voltage.
Malfunction
Decision
Conditions
Supposed
Causes
Power supply insufficient
Instantaneous failure
Open phase
Defect of inverter PC board
Defect of outdoor control PC board
Defect of K1M.
Main circuit wiring defect