Daikin RXY32MTL [124/346] Demand operation

Daikin RXY20MTLE [124/346] Demand operation
Si38-304 Other Control
Function 113
To inhibit the slave unit 2 from operating Set
setting mode 2 from No. 40 to No. 2.
(Procedure)
(1) Press and hold the MODE button (BS1) for 5 sec. or
more.
(2) Press the SET button (BS2) 40 times.
(3) Press the RETURN button (BS3) once.
(4) Press the SET button (BS2) once.
(5) Press the RETURN button (BS3) twice.
(6) Press the MODE button (BS1) once.
In the case of multi-outdoor-unit system, Inhibition of operation is not set with each
compressor individually.
In the case of multi-outdoor-unit system, when the above Inhibition of operation is set,
outdoor unit rotation is not functional.
5.3 Demand Operation
In order to save the power consumption, the capacity of outdoor unit is saved with control
forcibly by using Demand 1 Setting or Demand 2 Setting.
To operate the unit with this mode, additional setting of Continuous Demand Setting or
external input by external control adapter is required.
[Demand 1 setting]
[Demand 2 setting]
+
Other protection control functions have precedence over the above operation.
5.4 Heating operation prohibition
Heating operation is prohibited above 25°C ambient temperature.
LED display (
7
:ON
7
7
:OFF
9
9
:Blink)
H1P
---
H7P
(Factory set)
7
777777
777777
77
7
77
777
777
7
77777
77777
9
9
7
7777
7777
9
9
7
7
7
777777
777777
77
777
7777
7777
Note : Reset the power supply during the outdoor unit is stopping to cancel the
automatic backup operation forcibly.
Setting Standard for upper limit of power consumption
Demand 1 setting 1 Approx. 60%
Demand 1 setting 2 (factory setting) Approx. 70%
Demand 1 setting 3 Approx. 80%
Setting Standard for upper limit of power consumption
Demand 2 setting 2 (factory setting) Approx. 40%