Daikin RXY32MTL [328/346] Piping between the refnet joints

Daikin RXY10MYLE [328/346] Piping between the refnet joints
Si38-304 Selection of Pipe Size, Joints and Header
Appendix 317
6.1.4 Piping between the REFNET Joints
Select the proper pipe size using the following table based on the total capacity index of indoor
units connected downstream.
Connection piping size should not exceed the refrigerant piping size selected by "the model with
combination units".
6.1.5 Piping between the REFNET Joints and indoor unit
Pipe size for direct connection to indoor unit must be the same as the connection size of indoor
unit.
Connection pipe size of indoor unit.
6.1.6 The piping minimum thickness
Select the wall thickness in accordance with revelant local and national regulations.
Total capacity index Liquid Gas
<100 φ9.5 φ15.9
100x<160 φ9.5 φ19.1
160x<330 φ12.7 φ25.4
330x<480 φ15.9 φ34.9
480x<640 φ19.1 φ34.9
640 φ19.1 φ41.3
Total capacity index Liquid Gas
20, 25, 32, 40 φ6.4 φ12.7
50, 63, 80 φ9.5 φ15.9
100, 125 φ9.5 φ19.1
200 φ12.7 φ25.4
250 φ12.7 φ28.6
R22
Size Material Minimum thickness
t (mm)
φ6.4 O 0.8
φ9.5 O 0.8
φ12.7 O 0.8
φ15.9 O 1.0
φ19.1 O 1.0
φ22.2 1/2H 1.0
φ25.4 1/2H 1.2
φ28.6 1/2H 1.2
φ34.9 1/2H 1.3
φ41.3 1/2H 1.7
φ54.1 1/2H 1.7