Daikin RXY32MTL [164/346] Setting of low noise operation and demand operation

Daikin RXY38MYL [164/346] Setting of low noise operation and demand operation
Si38-304 Field Setting
Test Operation 153
3.2.3 Setting of Low Noise Operation and Demand Operation
Setting of Low Noise Operation
By connecting the external contact input to the low noise input of the outdoor unit external
control adapter (optional), you can lower operating noise by 2-3 dB.
A. When the low noise operation is carried out by external instructions (with the use
of the outdoor unit external control adapter)
1. Set External low noise / Demand YES/NO setting to External low noise / Demand YES.
(Set by Setting Mode 2)
2. Set External low noise level setting on the outdoor unit PC board, as the need arises.
(Lower noise operation can be carried out by Mode 2 than by Mode 1, and by Mode 3
than by Mode 2.)
3. Set Capacity precedence setting on the outdoor unit PC board, as the need arises.
(If set to ON, when air conditioning load gets higher, the low noise instructions are
neglected to switch to normal operation.) (Set by Setting Mode 2)
B. When the low noise operation is carried out automatically at night (The outdoor unit
external control adapter is not required)
1. Set Night-time low noise setting on the outdoor unit PC board. (Set by Setting Mode 2)
(Lower noise operation can be carried out by Mode 2 than by Mode 1, and by Mode 3
than by Mode 2.)
2. Set Night-time low noise start setting on the outdoor unit PC board, as the need arises.
(Set by Setting Mode 2)
(Since the time is presumed in accordance with the outdoor temperature, the starting time is
a target only.)
3. Set Night-time low noise end setting on the outdoor unit PC board, as the need arises.
(Set by Setting Mode 2)
(Since the time is presumed in accordance with the outdoor temperature, the ending time is
a target only.)
4. Set Capacity precedence setting on the outdoor unit PC board, as the need arises.
(Set by Setting Mode 2)
(If set to ON, when air conditioning load gets higher, the status is switched to normal
operation even at night.)

Содержание