Daikin RXY32MTL [117/346] Low pressure protection control

Daikin RXY18MYL [117/346] Low pressure protection control
Protection Control Si38-304
106 Function
4.2 Low Pressure Protection Control
This low pressure protection control is used to protect compressors against the transient
decrease of low pressure.
[In cooling operation]
+
In the case of multi-outdoor-unit system, the entire system performs this control in the
following sequence.
[In heating operation]
+
In the case of multi-outdoor-unit system, each outdoor unit performs this control
individually in the following sequence.
Low pressure not limited
Pe<0.16MPa
Low pressure standby
Low pressure limited
All STD compressors
stop.
Master unit:52 Hz + OFF + OFF
Slave unit:Stop
Pe<0.12MPa
Pe>0.20MPa
Pe<0.01MPa
Pe: LP pressure sensor detection
value for master unit
When occurring 3 times within 30 min.,
the malfunction code E4 is output.
Pe<0.00 MPa
Pe<0.02 MPa
Pe >0.04MPa
INV upper limit frequency = 210 Hz
Pe<0.04 MPa
&
Low pressure not limited
Low pressure standby
Low pressure limited
124 Hz + OFF + OFF
INV upper limit frequency: 1-step /
20 sec up from current compressor
frequency
52 Hz + OFF + OFF
Pe: LP pressure sensor detection
value for each outdoor unit
Pe>0.04 MPa
Pe<0.00 MPa
When occurring 3 times within 30 min.,
the malfunction code E4 is output.