Field Setting Si38-304
158 Test Operation
c
de
Setting
No.
Setting
contents
Setting No. indication Setting No. indication Setting
contents
Setting contents indication (Initial setting)
H1P H2P H3P H4P H5P H6P H7P H1P H2P H3P H4P H5P H6P H7P H1P H2P H3P H4P H5P H6P H7P
22 Night-time
low noise
setting
{zzzzzz{z { z { { z
OFF
(Factory
setting)
{zzzzz z
Mode 1
{zzzzz
Mode 2
{zzzz
Mode 3
{zzzz
25 External
low noise
setting
{ z { { z z {
Mode 1
{zzzzz
Mode 2
(Factory
setting)
{zzzz z
Mode 3
{zzzz z
26 Night-time
low noise
start setting
{ z { { z { z
PM 8:00
{zzzz z
PM 10:00
(Factory
setting)
{zzz z z
PM 0:00
{zzzz z
27 Night-time
low noise
end setting
{ z { { z { {
AM 6:00
{zzzz z
AM 7:00
{zzz z z
AM 8:00
(Factory
setting)
{zzzz z
29 Capacity
precedence
setting
{ z { { { z {
Low noise
precedence
(Factory
setting)
{zzzzz z
Capacity
precedence
{zzzz z
30 Demand
setting 1
{z{{{{z
60 % of
rated power
consumption
{zzzzz
70 % of
rated power
consumption
(Factory
setting)
{zzzzz
80 % of
rated power
consumption
{zzzzz
32
Continuous
demand
setting
{ z z z z z z
OFF
(Factory
setting)
{zzzz z
Continuous
demand 1
fixed
{zzzz z
12
External
low noise /
Demand
setting
{ z z { { z z
NO
(Factory
set)
{zzzzz {
YES
{zzzz{ z
Setting mode indication section Setting No. indication section Set contents indication section