Daikin RWEYQ26PY1 [152/342] In setting 1 push and hold the bs1 mode button for more than 5 seconds

Daikin RWEYQ30PY1 [152/342] In setting 1 push and hold the bs1 mode button for more than 5 seconds
Si30-813 Field Setting
Test Operation 141
Detailed Setting Procedure and Demand Control
1. Setting mode 1 (H1P off)
c
In setting mode 2, push the BS1 (MODE button) one time.
Setting mode 1 is entered and
H1P lights off.
During the setting mode 1 is displayed, “In low noise operation” and “In demand control” are
displayed.
2. Setting mode 2 (H1P on)
c
In setting 1, push and hold the BS1 (MODE button) for more than 5 seconds.
Setting
mode 2 is entered and H1P lights.
d
Push the BS2 (SET button) several times and match the LED display with the Setting No.
you want.
e
Push the BS3 (RETURN button) one time, and the present setting content is displayed.
Push the BS2 (SET button) several times and match the LED display with the setting
content (as shown below) you want.
f
Push the BS3 (RETURN button) two times.
Returns to
c
.
g
Push the BS1 (MODE button) one time.
Returns to the setting mode 1 and turns H1P off.
c
de
Setting
No.
Setting
contents
Setting No. indication Setting No. indication Setting
contents
Setting contents indication (Initial setting)
H1P H2P H3P H4P H5P H6P H7P H1P H2P H3P H4P H5P H6P H7P H1P H2P H3P H4P H5P H6P H7P
12
External
low noise /
Demand
setting
{ z z { { z z
NO
(Factory
set)
{zzzzz
l
YES
{zzzz
l
z
30 Demand
setting 1
{ z { { { { z
60 % of
rated power
consumption
{zzzz z
l
70 % of
rated power
consumption
(Factory
setting)
{zzzz
l
z
80 % of
rated power
consumption
{zzz
l
z z
32
Normal
demand
setting
{ z z z z z z
OFF
(Factory
setting)
{zzzz z
l
Continuous
demand 1
fixed
{zzzz
l
z
Setting mode indication section Setting No. indication section Set contents indication section