Daikin RWEYQ26PY1 [194/342] Normal

Daikin RWEYQ30PY1 [194/342] Normal
Si30-813 Troubleshooting by Indication on the Remote Controller
Troubleshooting 183
1: Coil check method for the moving part of the electronic expansion valve
Discount the electronic expansion valve from the PC board and check the continuity between
the connector pins.
(Normal)
{
: Continuity
× : No continuity
Pin No. 1. White 2. Yellow 3. Orange 4. Blue 5. Red 6. Brown
1. White × {
Approx.
300
× {
Approx.
150
×
2. Yellow × {
Approx.
300
× {
Approx.
150
3. Orange × {
Approx.
150
×
4. Blue × {
Approx.
150
5. Red ×
6. Brown
M
White (1)
Yellow
(2)
Blue
(4)
Brown
(6)
Red (5)
Orange (3)
φ1
φ2 φ4
φ3
(1) White
(2) Yellow
(3) Orange
(4) Blue
(5) Red
(6) Brown

Содержание