Daikin RWEYQ26PY1 [93/342] Special operation

Daikin RWEYQ30PY1 [93/342] Special operation
Special Operation Si30-813
82 Function
7. Special Operation
7.1 Oil Return Operation
In order to prevent the running-out of refrigerating machine oil in the compressor, the oil flowing
out from the compressor to the system side is collected through the oil return operation.
7.1.1 Oil Return Operation in Cooling Operation
[Starting conditions]
Start oil return operation in cooling operation referring to the following conditions.
* Cumulative oil return amount
* Timer
Cumulative compressor operating time after power supply turns on exceeds 2 hours and the
time after the completion of previous oil return operation exceeds 8 hours.
Furthermore, the cumulative oil return is calculated according to Tc, Te, and compressor load.
Cooling oil return
Parts name
Preperation
Electrical
symbol
Compressor
(M1C)
4 way valve (Main)
20S1 (Y5S)
4 way valve
(for heat exchanger)
20S2 (Y7S)
EV1 (Y1E)
EV3 (Y3E)
SVP (Y1S)
SVE (Y2S)
SVL (Y3S)
SVG (Y4S)
SVSL (Y6S)
(M1,2F)
Same as normal
cooling operation
Normal control
Thermostat off :
EV (Y1E)
Stop/thermostat off:
Normal control
200 pls
Thermostat ON:
Indoor unit control
(M1,2F)
EV (Y1E)
Ending condition
20 sec. Max.8 min. Max. 3min.
Thermostat on/Stop :
Indoor unit control
OFF
After oil return
operation
During oil return
operation
104 Hz
Sub-cooling
electronic
expansion valve
Hot gas bypass
solenoid valve
Main heat
exchanger
electronic
expansion valve
Water heat exch.
oil return solenoid
valve
Receiver gas
charging solenoid
valve
Receiver gas
discharge solenoid
valve
Liquid pipe stop
solenoid valve
Indoor cooling unit
fan
Indoor cooling unit
expansion valve
Indoor heating unit
fan
Indoor heating unit
expansion valve
52 Hz
OFF
OFF
2000 pulse
0 pulse
ON
OFF
ON
OFFOFF
ON
OFF
OFF
2000 pulse
0 pulse
ON
OFF
OFFOFF
Symbol