Daikin RWEYQ26PY1 [198/342] After confirmation turn off the power take off the short circuit and connect x70a back to original condition

Daikin RWEYQ30PY1 [198/342] After confirmation turn off the power take off the short circuit and connect x70a back to original condition
Si30-813 Troubleshooting by Indication on the Remote Controller
Troubleshooting 187
Troubleshooting
1. Pull out and insert the connecter once and check it is absolutely connected.
2. Method to check transmission part of indoor PC board.
Turn off the power and remove the connecter X70A of indoor PC board (A1P).
Short-circuit X70A.
After turning on the power, check below numbers under local setting remote control.
(Confirmation: Setting position NO. at the condition of setting switch No. 21 on mode No.
41)
After confirmation, turn off the power, take off the short-circuit and connect X70A back to
original condition.
Determination 01: Normal
Other than 01: Transmission defect on indoor PC board
NO
Is the connector
between indoor PC board (A1P) and
PC board for fan (A2P) accurately
connected? (*1)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Connect the connector accurately.
NO
Under
above local installation
mode, installation position is
"
01
".
Replace indoor PC board (A1P).
Confirm the condition of
transmission on indoor PC
board using local installation
mode. (*2)
Connect the connecter X70A
and turn on the power again.
NO
YES
YES
YES
"C1"
Malfunction breaks out
again.
Replace PC board for fan (A2P).
Connect it and operate (It is
possible to have a cause, such
as instantaneous blackout)