Daikin RWEYQ26PY1 [81/342] Heating start up control

Daikin RWEYQ30PY1 [81/342] Heating start up control
Startup Control Si30-813
70 Function
4.2 Heating Start-up Control
Both master and slave units operate same time for changing 4 way valve position
Normal
operation after completion.
Parts name Symbol
Electrical
symbol
Pressure equalization
control before start-up
Starting control
Compressor (M1C) 0 Hz
52Hz
+2 steps/20 sec.
(till Pc-Pe >0.49 MPa)
Inverter cooling fan (M1,2F) OFF
Inverter cooling fan
control
4 way valve (Main) 20S1 (Y5S) Holding ON
4 way valve (for heat exchanger) 20S2 (Y7S) Holding OFF
Main heat exchanger electronic exp. valve EV1 (Y1E) 0 pulse 180 pulse
Sub-cooling electronic exp. valve EV3 (Y3E) 0 pulse 0 pulse
Hot gas bypass solenoid valve SVP (Y1S) OFF ON
Water heat exch. oil return solenoid valve SVE (Y2S) OFF OFF
Receiver gas charging solenoid valve SVL (Y3S) OFF OFF
Receiver gas discharge solenoid valve SVG (Y4S) OFF OFF
Non-operation unit liquid pipe stop
solenoid valve
SVSL (Y6S) ON ON
Indoor unit fan (M1,2F) Indoor unit controlIndoor unit control
Indoor unit expansion valve EV (Y1E) 0 pulse Indoor unit control
Ending condition 1 minute
Max. 6 minutes 40 sec.
Thermostat ON