Daikin RWEYQ26PY1 [185/342] Troubleshooting

Daikin RWEYQ30PY1 [185/342] Troubleshooting
Troubleshooting by Indication on the Remote Controller Si30-813
174 Troubleshooting
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Remove the foreign particles.
Connect properly.
Replace the fan motor.
Refer to the figure in following
page.
Replace the fan motor.
NO
YES
NO
YES
NO
YES
NO
Are there
foreign particles
around the fan?
Are the
harness from the
fan motor and the harness
of A1P fan motor (fixed to
X20A) connected
properly?
Can the
fan be removed
from the junction connector
between the fan motor and A1P
and rotated easily
with hands?
YES
Turn off the power supply.
Check the fan motor
connector.
Does the
resistance between pins
satisfy the judgment
criteria?
Connect properly.
Replace the indoor PC board.
YES
NO
Are
heavy current PC board
(A1P) and low current PC board
(A2P) connected
properly?