Daikin RWEYQ26PY1 [240/342] Malfunction of transmission between indoor units

Daikin RWEYQ30PY1 [240/342] Malfunction of transmission between indoor units
Si30-813 Troubleshooting by Indication on the Remote Controller
Troubleshooting 229
2.43
U4
Malfunction of Transmission between Indoor Units
Remote
Controller
Display
U4
Applicable
Models
Indoor unit
FXFQ, FXCQ, FXKQ, FXDQ, FXSQ, FXMQ, FXHQ, FXAQ, FXLQ, FXNQ, FXUQ
Outside unit
RWEYQ8P, 10P
Method of
Malfunction
Detection
Microcomputer checks if transmission between indoor and outside units is normal.
Malfunction
Decision
Conditions
When transmission is not carried out normally for a certain amount of time
Supposed
Causes
Indoor to outdoor, outside to outside unit transmission wiring F1, F2 disconnection, short
circuit or wrong wiring
Outside unit power supply is OFF
System address doesn’t match
Defect of indoor unit PC board
Defect of outside unit PC board