Daikin RWEYQ26PY1 [275/342] Dirty evaporator

Daikin RWEYQ30PY1 [275/342] Dirty evaporator
Troubleshooting (OP: Unified ON/OFF Controller) Si30-813
264 Troubleshooting
Check for causes of wet operation
CHECK 4
1 : In cooling, the indoor unit electronic expansion valve is used for “superheated degree control”. (Refer to page 95.)
2 : In heating, the outside unit electronic expansion valve (Y1E) is used for “superheated degree control”. (Refer to page
73.)
3 : Reference values for superheated degree to be used in the judgment of wet operation
Suction gas superheated degree: 3°C or less Discharge gas superheated degree: 15°C or less, excluding
when it is immediately after startup, under drop control or other specific conditions.
(The values above must be used only for reference purposes. Even it is operated within the range above,
operation may be normal in other conditions.)
Dwelled
refrigerant
Faulty indoor
unit electronic
expansion valve
Faulty outside
unit electronic
expansion valve
Faulty crankcase heater
Faulty
superheated
degree control
Wet operation
[In cooling]
Degradation in
evaporation
capacity
[In heating]
Does the water pump function normally?
Is the strainer or other parts clogged?
Is the water heat exchanger clogged?
Is there any obstacle in the
air passage?
Is the air filter clogged?
Can the fan motor be rotated with hands?
Are the motor coil resistance and
insulation normal?
Are the coil resistance and insulation normal?
Is the connector properly connected?
Are the thermistor resistance characteristics
normal?
Is the connector properly connected?
Are the thermistor resistance
characteristics normal?
Are the coil resistance and insulation normal?
Are the voltage characteristics normal?
Is the connector properly connected?
Are the thermistor resistance characteristics normal?
Does the pressure value of the Service Checker
match the reading of the pressure sensor?
Is the heat exchanger clogged?
Referring to the Fault Tree Analysis (FTA) shown below, identify the faulty points.
Excessive refrigerant
charging
[In cooling]
If the indoor unit
electronic
expansion valve
excessively
opened
(1)
[In heating]
If the outside unit
electronic
expansion valve
excessively
opened
(2)
Frequent starts and
stops of the compressor
Faulty control
Faulty control
Dirty evaporator
Decreased
fan airflow
rate
Decreased
fan output
High air
passage
resistance
Faulty valve coil
Faulty valve body
Faulty control PC board
Faulty control PC board
Faulty fan motor
Dirty filter
Obstacle
Clogged water piping system
Faulty water pump
Dirty water heat exchanger
Decrease in
water of the
water heat
exchanger
Faulty control PC board
(including capacity setting)
Faulty valve coil
Faulty valve body
Faulty low pressure sensor
Faulty suction pipe thermistor
Faulty gas pipe thermistor
of indoor unit
Faulty liquid pipe thermistor
of indoor unit
Refer to CHECK 5