Daikin RWEYQ26PY1 [318/342] Example of connection

Daikin RWEYQ30PY1 [318/342] Example of connection
Si30-813 Example of Connection
Appendix 307
5. Example of Connection
* Below table is mentioned about the case of heat recovery system (3-piping: suction gas, HP/LP gas and liquid pipes).
In case of heat pump system (2-piping: gas and liquid pipes), select the pipe size from suction gas pipe for gas pipes and from liquid gas pipe for liquid pipes. And BS unit is not required.
Example of connection
(Connection of 8 indoor units Heat pump system)
Single outside
unit system
a
b
k
i
j
c
de
s
c
am
b
r
qom
n
p
Outside unit
Outside unit
Outside unit
Outside unit
REFNET joint (A-G)
REFNET joint (A-G)
REFNET joint (A·B)
REFNET joint (A·B)
REFNET header
REFNET header
REFNET header
REFNET header
BS units
( B1 - B4 )
Multi outside
unit system
Maximum
allowable
length
Between outside
(
)
and indoor units
Between outside branch and outside unit
(In case of multi system)
Between outside and indoor units
Between indoor and indoor units
Between outside and outside units
Actual pipe length
Actual pipe length
Actual pipe length
Difference in height
Difference in height
Difference in height
Equivalent length
Total extension length
Pipe length between outside () and indoor units 120m
(Example 1,4) unit 8 : a + b + c + d + e + s 120m
(Example 1,4) unit 8 : b + c + d + e + s 40m
Equivalent pipe length between outside () and indoor units 140m (Note 1) (assume equivalent pipe length of REFNET joint to be 0.5m, that of REFNET header to be 1m, BSVP100,160 is 4 m and BSVP250 is 6m.)
Piping length from outside branch to outside unit 10m Equivalent length: max 13m
Difference in height between outside and indoor units (H1) 50m (Max 40m if the outside unit is below)
Difference in height between indoor units (H2) 15m
Difference in height between outside unit (main) and outside unit (sub) (H3) 2m
Pipe length from first refrigerant branch kit (either REFNET joint or REFNET header ) to indoor unit 40m (Note 2)
Total piping length from outside unit () to all indoor units 300m
Allowable
height
length
Allowable length after the branch
(Example 3,6) unit 8 : a + o 120m
(Example 2,5) unit 6 : a + b + l 120m, 8 : a + m + n + p 120m
(Example 3,6) unit 8 : o 40m(Example 2,5) unit 6 : b + l 40m, 8 :m + n + p 40m
r 10m (
Equivalent length
13m)
u+s 10m (
Equivalent length
13m)
u+t 10m (
Equivalent length
13m)
Refrigerant branch kits can only be
used with R-410A.
How to select REFNET joint:
When using REFNET joints at the first branch counted from the outside unit side.
Choose from the following table in accordance with the capacity of the outside unit.
(Example 1,2,4,5 : REFNET joint
A
)
Piping between outside unit (
) and refrigerant branch kit (part A)
Piping between outside branch and outside unit (part C)
• Match
to the size of connection piping of outside unit
Piping between outside branches (part B)
Select the size from the following table based on the total capacity of the
outside unit to be connected to upstream
Additional referigerant to be charged R (kg)
(R should be rounded off in units of 0.1kg.)
RWEYQ10 type
RWEYQ20 type
RWEYQ30 type
KHRP25A33T
KHRP25A72T + KHRP25M72TP
KHRP25A73T + KHRP25M73TP
KHRP26A33T
KHRP26A72T
KHRP26A73T + KHRP26M73TP
For REFNET joints other than the first branch, select the proper branch kit model based on the total capacity index.
< 200
200 x< 290
290 x< 640
640
KHRP25A22T
KHRP25A33T
KHRP25A72T+KHRP25M72TP
KHRP25A73T+KHRP25M73TP
KHRP26A22T
KHRP26A33T
KHRP26A72T
KHRP26A73T+KHRP26M73TP
How to select REFNET header
Select suitable one from the table below according to the total capacity of indoor units to be connected to the downstream of REFNET header.
Be careful that 250 type cannot be connected to the downstream of REFNET header.
< 200
200 x< 290
290 x< 640
640
KHRP25M33H
KHRP25M72H+KHRP25M72HP
KHRP25M73H+KHRP25M73HP
KHRP26M72H
KHRP26M33H
KHRP26M22H, KHRP26M33H
KHRP26M73H+KHRP26M73HP
How to select an outside branch kit (Needed when the outside unit type is RWEYQ20 or more.)
Select from the table below according to the number of outside units.
2 unit
3 unit
BHFP22MA56
BHFP22MA84
BHFP26MA56
BHFP26MA84
(Example 1,4) In case of REFNET Joint
C
, indoor units of 5 + 6 + 7 + 8
(Example 2,5) In case of REFNET Joint
B
, indoor units of 7 + 8
(Example 2,5) In case of REFNET Header, indoor units of 1 + 2 + 3 + 4 + 5 + 6
(Example 3,6) In case of REFNET Header,
indoor units of 1 + 2 + 3 + 4 + 5 + 6 + 7 + 8
Example of downstream indoor units
φ22.2 × 0.80
φ28.6 × 0.99
φ34.9 × 1.21 φ28.6 × 0.99 φ19.1 × 0.80
φ19.1 × 0.80
φ22.2 × 0.80
φ 9.5 × 0.80
φ15.9 × 0.99
RWEYQ10
RWEYQ20
RWEYQ30
Piping between refrigerant branch kit and refrigerant branch kit/BS unit
Piping between BS unit and refrigerant branching kit
Select one from the table below according to the total capacity of indoor units to be
connected to downstream.
For the gas piping size in case of 2-tube piping between refrigerant branching kit/BS
unit and refrigerant branching kit, select the size of suction gas piping.
The size of connection piping should not exceed the refrigerant piping size selected
under the generic term of the system.
Piping between BS unit (refrigerant branch kit) and indoor unit
Match to the size of the connection piping on the indoor unit.
a:φ19.1×30m
b:φ15.9×10m
c:φ09.5×10m
d:φ 9.5×10m
e:φ 9.5×10m
f:φ 9.5×10m
g:φ06.4×10m
h:φ 6.4×20m
i:φ12.7×10m
j:φ 6.4×10m
k:φ 6.4×10m
l:φ 6.4×10m
m
: φ 6.4×10m
n:φ 6.4×10m
o:φ06.4×10m
p:φ 6.4×10m
r:φ 9.5× 3m
s:φ09.5× 3m
t:φ09.5× 3m
u:φ15.9× 1m
R= +
Indoor capacity index
Refrigerant branch kit name
Number of units of outside unit
Heat recovery system
In case of 2-tube piping
Heat pump system
In case of 3-tube piping
In case of 3-tube piping In case of 2-tube piping
Outside unit capacity type
Refrigerant branch kit name
Indoor capacity index
Refrigerant branch kit name
Suction gas pipe
Capacity type
of outside unit
Piping size (outer diameter × Min. thickness)
HP/LP gas pipe Liquid pipe
+ +
+
+
+
(Heat recovery system)
If the outside unit is
RWEYQ30 and the piping
lengths are as at right
R= 30 0.26 + 11 0.18 + 10 0.12 + 49 0.059 + 100 0.022 + 9 = 25.071
b+ua c +d+e+f+r+s+t g+h+j+k+l+m+n+o+pi
25.1 (kg)
Total length (m) of liquid
piping size at
φ
22.2
×0.37
(kg/m)
Total length (m) of liquid
piping size at
φ9.5
Total length (m) of liquid
piping size at
φ6.4
Total length (m) of liquid
piping size at
φ
19.1
Total length (m) of liquid
piping size at
φ15.9
Total length (m) of liquid
piping size at
φ12.7
×0.26
(kg/m)
×0.18
(kg/m)
×0.12
(kg/m)
×0.059
(kg/m)
×0.022
(kg/m)
System name
RWEYQ10
RWEYQ20
RWEYQ30
3 kg
4.5 kg
6 kg
4 kg
6.5 kg
9 kg
Heat recovery systemHeat pump system
Example for refrigerant branch using REFNET joint and REFNET header for RWEYQ30
Caution
The thickness of the pipes in the table shows the requirements of Japanese
High Pressure Gas Control low. (As of Jan. 2003)
The thickness and material shall be selected in accordance with local code.
Refrigerant branch kit selection
Pipe size selection
For a multi outside unit system, make the settings in accordance with
the following figure.
Piping between outside unit (
) and refrigerant branch kit (part A)
Piping between outside branches (part B)
Piping between outside branch and outside unit (part C)
How to calculate the additional refrigerant
to be charged
Outside unit
r
s
u
Heat recovery system Heat pump system
φ15.9 × 0.99
φ19.1 × 0.80
φ22.2 × 0.80
φ28.6 × 0.99
φ12.7 × 0.80
φ15.9 × 0.99
φ19.1 × 0.80
φ28.6 × 0.99
φ34.9 × 1.21
φ41.3 × 1.43
φ28.6 × 0.99
(Unit:mm)Indoor unit connection piping size
Indoor units
( 1 - 8 )
Heat recovery system
( 1 - 6 )
Cooling only
( 7
·
8 )
BS units
( B1 - B4 )
Indoor units
( 1 - 8 )
Heat recovery
system ( 1 - 6 )
Cooling only
( 7
·
8 )
BS units ( B1 - B5 )
BS units
( B1 - B5 )
Indoor units
( 1 - 8 )
Heat recovery system
( 1 - 4 , 7 · 8 )
Indoor units
( 1 - 8 )
Cooling only
( 5
·
6 )
l
f
g
a
b
c
d
e
h
H2
H1
H1
1
1234567
8
234567
1
1
2
3
456
7
8
23456
7
8
8
B2
B3 B4
B1
B1
B2 B3 B4
B5
B2 B3 B4
B5
d
e
f
g
h
i
j
k
l
m
a
a
b
a
b
d
f
c
e
g
f
h
j
d
c
e
gi k
l
m
n
o
b
Outside unit
Outside
unit
1
123
456 7
8
2
34567
8
B1 B2 B3 B4 B5 B6
B6B5B4B3B2B1
BS units
( B1 - B6 )
BS units
( B1 - B6 )
Indoor units
( 1 - 8 )
Heat recovery system
( 1 - 6 )
Heat recovery
system ( 1 - 6 )
Indoor units
( 1 - 8 )
Cooling only
( 7
·
8 )
Cooling only
( 7
·
8 )
First outside
branch
s
r
p
q
n
o
k
i
l
j
h
g
f
H3
H1
H2
h
i
j
k
l
m
n
o
BS
unit
Outside unit
side
(Thick line): 3-piping
Indoor unit
side
(3-piping) (2-piping)
HP/LP gas piping
Gas piping
Liquid piping
Liquid piping
Suction gas piping
• Piping between outside unit and BS unit
HP/LP gas piping
Suction gas piping
Liquid piping
(Thin line): 2-piping
• Piping between BS unit and indoor unit,
Gas piping
Liquid piping
In case of multi outside unit system, re-read the
[outside unit] as [the first outside branch seen from the
indoor unit side].
[]
Corrected
volume by
outside unit
t
H1
H2
Heat recovery system
( 1 - 4 , 7 · 8 )
Cooling only
( 5
·
6 )
m
Branch with REFNET joint
Branch with REFNET joint and REFNET header
Branch with REFNET header
Example 1
Example 4
Example 2
Example 5
Example 3
Example 6
(Unit: mm)
(Unit: mm)
φ28.6 × 0.99
φ22.2 × 0.80
φ15.9 × 0.99
RWEYQ20
Suction gas pipe
Total capacity
of outside unit
Piping size (outer diameter × Min. thickness)
HP/LP gas pipe Liquid pipe
φ19.1 × 0.80
φ 9.5 × 0.80
φ12.7 × 0.80
φ15.9 × 0.99
< 150
150 x< 200
200 x< 290
290 x< 420
420 x< 640
640 x< 920
920
Suction gas pipe
Indoor capacity index
Piping size (outer diameter × minimum wall thickness)
HP/LP gas pipe
Liquid pipe
(Unit: mm)
φ12.7 × 0.80
φ15.9 × 0.99
φ19.1 × 0.80
φ22.2 × 0.80
φ6.4 × 0.80
φ9.5 × 0.80
φ9.5 × 0.80
20, 25, 32, 40, 50 type
63, 80, 100, 125 type
200 type
250 type
Gas pipe
Indoor capacity type
Piping size (outer diameter × minimum
wall thickness)
Liquid pipe
B1
B1 B2 B3 B4
np
o
H2
c
d
e
f
g
h
i
j
k
l
n
p
o
u
t
s
r
H3
H2
H1
H3
H1
H2
A
B
A
AB
CDE
B
F
ABCDE
G
FG