Daikin RWEYQ26PY1 [79/342] Standby

Daikin RWEYQ30PY1 [79/342] Standby
Standby Si30-813
68 Function
3. Standby
3.1 Restart Standby
Forced standby is performed to prevent frequent repetition of ON/OFF of the compressor, and
to equalize pressure in the refrigerant system.
3.2 Crankcase Heater Control
In order to prevent the refrigerant from dwelling in the compressor in the stopped mode, this
mode is used to control the crankcase heater.
Parts name Symbol
Electrical
symbol
Actuator function
Compressor (M1C) 0 Hz
Inverter cooling fan (M1,2F) OFF
4 way valve (Main) 20S1 (Y5S) Holding
4 way valve (for heat exchanger) 20S2 (Y7S) Holding
Main heat exchanger electronic exp.
valve
EV1 (Y1E) 0 pulse
Sub-cooling electronic exp. valve EV3 (Y3E) 0 pulse
Hot gas bypass solenoid valve SVP (Y1S) OFF
Water heat exch. oil return solenoid valve SVE (Y2S) OFF
Receiver gas charging solenoid valve SVL (Y3S) OFF
Receiver gas discharge solenoid valve SVG (Y4S) OFF
Non-operation unit liquid pipe stop
solenoid valve
SVSL (Y6S) ON
Indoor cooling unit fan (M1, 2F) Remote controller setting
Indoor cooling unit expansion valve EV (Y1E) All indoor EV 0 pulse
Indoor heating unit fan (M1, 2F) Indoor unit control
Indoor heating unit expansion valve EV (Y1E) All indoor EV 0 pulse
BS unit Holding
Ending condition 4 minutes
Crankcase heater
OFF
Crankcase heater
ON
Discharge pipe temp.<70˚C
Discharge pipe temp.>75˚C