Daikin RWEYQ26PY1 [272/342] High ambient temperature

Daikin RWEYQ30PY1 [272/342] High ambient temperature
Si30-813 Troubleshooting (OP: Unified ON/OFF Controller)
Troubleshooting 261
Check for causes of rise in high pressure
CHECK 1
Is the indoor unit too small for the large-sized outside unit?
Referring to the Fault Tree Analysis (FTA) shown below, identify the faulty points.
Rise in high
pressure
Local
pressure
rise
Faulty high
pressure
control
Faulty outside
unit electronic
expansion valve
Faulty
control
Faulty indoor
unit electronic
expansion valve
Stop valve closed
Faulty high pressure sensor
[In cooling]
If the outside unit
electronic
expansion valve
is throttled
(1)
Dirty water heat exchanger
Decrease in water
of the water heat
exchanger
Mixing-in of non-condensable gas
Degradation in
condensing
capacity
Clogged water piping system
[In cooling]
[In heating]
Check to be sure the stop valve is open.
Conduct visual checks for pipe conditions.
Is there any temperature difference around
the filter or the branch pipe?
Are the coil resistance and insulation normal?
Are the voltage characteristics normal?
Does the pressure value of the Service
Checker match the reading of the
pressure sensor?
Are the coil resistance and insulation normal?
Are the voltage characteristics normal?
Is the connector properly connected?
Are the thermistor resistance characteristics
normal?
Does the pressure value of the Service
Checker match the reading of the pressure
sensor?
Is the heat exchanger clogged (in cooling)?
Is air or else mixed in the refrigerant system?
Is the water temperature at the inlet not
more than 45°C?
Does the water pump function normally?
Is the strainer or the like clogged?
Is the suction air temperature not more
than 27°C?
Is air or else mixed in
the refrigerant system?
Is the indoor temperature not more
than 27°C?
Is the connector properly connected?
Are the thermistor resistance
characteristics normal?
Can the fan motor be rotated with hands?
Are the motor coil resistance and
insulation normal?
If a spare PC board is mounted, is the
capacity setting properly made?
Is the air filter clogged?
Is there any obstacle in the air
passage?
Excessive refrigerant charging
Improper mode selection
[In heating]
1 : In cooling, the outside unit electronic expansion valve (Y1E) is fully open in normal condition.
2 : In heating, the indoor unit electronic expansion valve is used for “subcooled degree control”.
(Refer to “Electronic Expansion Valve Control” on page 95)
[In heating]
If the indoor unit
electronic
expansion valve
excessively throttled
(2)
High pipe
resistance
A temperature difference in
excess of 10°C between the inlet and
the outlet is deemed to be abnormal.
Faulty
control
Bent and Crush of
pipe
Clogging of foreign
particles
Faulty valve coil
Faulty valve body
Faulty high pressure sensor
Faulty control PC board
Faulty indoor unit
liquid pipe thermistor
Faulty valve coil
Faulty valve body
Faulty control PC board
High water temperature at the water heat exchanger inlet
Faulty water pump
Short circuit
High ambient temperature
Faulty fan motor
Dirty filter
Obstacle
Faulty control PC
board (including
capacity setting)
Mixing-in of non-condensable gas
High suction air
temperature of
indoor unit
Decreased
fan airflow
rate
Decreased
fan output
High air
passage
resistance
Faulty suction air thermistor of indoor unit
Refer to CHECK 5