Daikin RWEYQ26PY1 [216/342] Troubleshooting

Daikin RWEYQ30PY1 [216/342] Troubleshooting
Si30-813 Troubleshooting by Indication on the Remote Controller
Troubleshooting 205
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
YES
YES
YES
NO
NO
NO
1: For thermistor temperature and resistance characteristics,
refer to page 309, 310.
There is a possibility that there are other causes of
refrigerant overfilling.
:
Refer to page 264 to eliminate the causes
of wet operation.
CHECK 4
Mount the thermistor properly
before operation.
Replace the thermistor if it
functions abnormally before
operation.
Continue operation.
Is the
thermistor mounted
properly?
Check the mounting condition
of the suction pipe thermistor
and the subcooling heat
exchanger outlet thermistor
temperature sensor mounted
to piping.
Remove the suction pipe
thermistor and the subcooling
heat exchanger outlet
thermistor from the outside
unit PC board and measure
the resistance with a tester.
Carry out check operation again.
Does
it function normally?
(1)
Does the
abnormal code (F6)
repeat?