Daikin RWEYQ26PY1 [231/342] Troubleshooting

Daikin RWEYQ30PY1 [231/342] Troubleshooting
Troubleshooting by Indication on the Remote Controller Si30-813
220 Troubleshooting
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
The
transmission
wiring between the
outside unit PC board
inverter unit is
disconnected.
YES
Fix the disconnection and turn on
again.
Connect transmission wiring and
turn on again.
NO
YES
The
microcomputer
monitor (green) on
the inverter PC board
is blinking.
The voltage
between two pins
of X1A on the inverter
unit is 220 ~ 240 V.
Defect of outside unit main PC
board or defect of inverter PC
board.
Check the noise filter (Z1F) for
disconnection, and check the
power supply wiring of the inverter
PC board.
Replace inverter PC board.
When the LC malfunction occur
again, replace control PC board.
YES
NO
NO
YES
NO
Are the
connectors
between the main
PC board (A1P),
and inverter PC board
(A2P) connected
securely?