Daikin RWEYQ26PY1 [224/342] Outside unit malfunction of discharge pipe pressure sensor

Daikin RWEYQ30PY1 [224/342] Outside unit malfunction of discharge pipe pressure sensor
Si30-813 Troubleshooting by Indication on the Remote Controller
Troubleshooting 213
2.30
JA
Outside Unit: Malfunction of Discharge Pipe Pressure
Sensor
Remote
Controller
Display
JA
Applicable
Models
Outside unit
RWEYQ8P, 10P
Method of
Malfunction
Detection
Malfunction is detected from the pressure detected by the high pressure sensor.
Malfunction
Decision
Conditions
When the discharge pipe pressure sensor is short circuit or open circuit.
Supposed
Causes
Defect of high pressure sensor system
Connection of low pressure sensor with wrong connection.
Defect of outside unit PC board.
Troubleshooting
1: Voltage measurement point
2: Refer to pressure sensor, pressure / voltage characteristics table on P.311.
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
The
relationship
between the 1
VH and high pressure
is normal (see 2) when
voltage is measured between
X46A pins (1) and (3) of
outside unit PC
board (A1P)
(see 1).
Replace the high pressure sensor.
Connect the high pressure sensor
and turn on again.
NO
NO
Replace outside unit PC board
A1P.
YES
YES
The high
pressure sensor is
connected to X46A of
outside unit PC
board (A1P).