Daikin RWEYQ26PY1 [90/342] Discharge pipe protection control

Daikin RWEYQ30PY1 [90/342] Discharge pipe protection control
Si30-813 Protection Control
Function 79
6.3 Discharge Pipe Protection Control
This discharge pipe protection control is used to protect the compressor internal temperature
against a malfunction or transient increase of discharge pipe temperature.
Discharge pipe protection control is carried out in each outside unit.
[INV compressor]
HTdi :Value of INV compressor discharge pipe
temperature (Tdi) compensated with
outdoor air temperature
Discharge pipe
temp.control standby
HTdi > 135˚C
HTdi > 120˚C for 10 min. or more.
or
HTdi>130˚C
HTdi>120˚C
for 5 min.
or
HTdi < 100˚C
HTdi < 110˚C
HTdi > 115˚C
HTdi > 115˚C
When occurring 3 times within 100 minutes,
the malfunction code “F3” is output.
Normal operation
Compressor upper limit down 1 step/30 sec.
Compressor 62Hz
Compressor upper limit up 1 step/20 sec.
Less than 2 times within
100 min.