Daikin RWEYQ26PY1 [223/342] Malfunction of sub cooling heat exchanger outlet thermistor r5t

Daikin RWEYQ30PY1 [223/342] Malfunction of sub cooling heat exchanger outlet thermistor r5t
Troubleshooting by Indication on the Remote Controller Si30-813
212 Troubleshooting
2.29
J9
Malfunction of Sub Cooling Heat Exchanger Outlet
Thermistor (R5T)
Remote
Controller
Display
J9
Applicable
Models
Outside unit
RWEYQ8P, 10P
Method of
Malfunction
Detection
Malfunction is detected according to the temperature detected by sub cooling heat exchanger
outlet thermistor.
Malfunction
Decision
Conditions
When the sub cooling heat exchanger outlet thermistor is short circuited or open.
Supposed
Causes
Faulty receiver gas pipe thermistor (R5T)
Faulty outside unit PC board
Troubleshooting
1: Refer to thermistor resistance / temperature characteristics table on P.309.
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Is the
resistance
measured after
removing the thermistor
(R5T) from outside unit PC
board normal?
(3.5 k to
360 k)
1
Replace outside unit PC board
(A1P).
Connect the connector and operate
unit again.
NO
NO
Replace thermistor (R5T).
YES
YES
Is
the connector
for oil equalizing
pipe thermistor
connected to X37A on
outside unit PC
board (A1P)?