Daikin RWEYQ26PY1 [97/342] Heating simultaneous cooling heating mode

Daikin RWEYQ30PY1 [97/342] Heating simultaneous cooling heating mode
Special Operation Si30-813
86 Function
7.3.2 Heating & Simultaneous Cooling/Heating Mode
Parts name Symbol
Electrical
symbol
Master unit operation Slave unit operation
Compressor (M1C) Current step OFF
Inverter cooling fan (M1,2F) Inverter cooling fan control Inverter cooling fan control
4 way valve 1 20S1 (Y5S) ON ON
4 way valve 2 20S2 (Y7S) Holding Holding
Main heat exchanger
electronic exp. valve
EV1 (Y1E)
20S2=OFF: 2000 pulse
20S2=ON
: 0 pulse
0 pulse
Sub-cooling electronic
exp. valve
EV3 (Y3E) 0 pulse 0 pulse
Hot gas bypass solenoid
valve
SVP (Y1S) ON OFF
Water heat exch. oil return
solenoid valve
SVE (Y2S) OFF OFF
Receiver gas charging
solenoid valve
SVL (Y3S) OFF OFF
Receiver gas discharge
solenoid valve
SVG (Y4S) OFF OFF
Non-operation unit liquid
pipe stop solenoid valve
SVSL (Y6S) OFF ON
Indoor cooling unit fan (M1,2F) No instruction
Indoor cooling unit
expansion valve
EV (Y1E) All 0 pulse
Indoor heating unit fan (M1,2F) No instruction
Indoor heating unit
expansion valve
EV (Y1E) All 500 pulse
Ending condition Max. 5 min.