Daikin RWEYQ26PY1 [258/342] Address duplication improper setting

Daikin RWEYQ30PY1 [258/342] Address duplication improper setting
Si30-813 Troubleshooting (OP: Central Remote Controller)
Troubleshooting 247
3.4
MC
Address Duplication, Improper Setting
Remote
Controller
Display
MC
Applicable
Models
Central remote controller
Method of
Malfunction
Detection
Detect the malfunction according to DIII-NET transmission data.
Malfunction
Decision
Conditions
Two units are both set to master controller mode or slave controller mode.
Supposed
Causes
Address duplication of centralized remote controller
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Are
two or more central
remote controllers
connected?
Disconnect all central remote
controllers except one and
reset the power supply of the
central remote controller.
Reset power supply of the
central remote controller.
NO
YES