Daikin RWEYQ26PY1 [222/342] Malfunction of liquid pipe thermistor r6t

Daikin RWEYQ30PY1 [222/342] Malfunction of liquid pipe thermistor r6t
Si30-813 Troubleshooting by Indication on the Remote Controller
Troubleshooting 211
2.28
J7
Malfunction of Liquid Pipe Thermistor (R6T)
Remote
Controller
Display
J7
Applicable
Models
Outside unit
RWEYQ8P, 10P
Method of
Malfunction
Detection
Malfunction is detected according to the temperature detected by receiver outlet liquid pipe
thermistor.
Malfunction
Decision
Conditions
When the liquid pipe thermistor is short circuited or open.
Supposed
Causes
Faulty liquid pipe thermistor (R6T)
Faulty outside unit PC board
Troubleshooting
1: Refer to thermistor resistance / temperature characteristics table on P.309.
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Is the
resistance
measured after
removing the thermistor
(R6T) from outside unit PC
board normal?
(3.5 k to
360 k)
1
Replace outside unit PC board
(A1P).
Connect the connector and operate
unit again.
NO
NO
Replace thermistor (R6T).
YES
YES
Is
the connector
for receiver
outlet liquid pipe thermistor
connected to X37A on
outside unit PC
board (A1P)?