Daikin RWEYQ26PY1 [274/342] Faulty low pressure sensor

Daikin RWEYQ30PY1 [274/342] Faulty low pressure sensor
Si30-813 Troubleshooting (OP: Unified ON/OFF Controller)
Troubleshooting 263
Check for causes of overheat operation
CHECK 3
(1)
Faulty hot
gas bypass
control
[In cooling only]
(2)
Faulty indoor unit
electronic
expansion valve
Faulty control
Faulty outside
unit electronic
expansion valve
Clogged hot gas passage
Are the coil resistance and insulation normal?
Are the coil resistance and insulation
normal?
Are the voltage characteristics normal?
Is the connector properly connected?
Are the thermistor resistance
characteristics normal?
Does the pressure value of the Service
Checker match the reading of the
pressure sensor?
Is the temperature of piping connected to the
four-way changeover valve normal?
Are the coil resistance and insulation normal?
Are the coil resistance and insulation normal?
Are the voltage characteristics normal?
Is the connector properly connected?
Are the thermistor resistance characteristics
normal?
Does the pressure value of the Service Checker
match the reading of the pressure sensor?
Is the piping length in the permissible range?
Conduct visual checks for pipe conditions.
Eliminate moisture by vacuum break.
Check to be sure the stop valve is open.
1 : For hot gas bypass control, refer to “Low Pressure Protection Control” on page 77.
2 : For subcooling electronic expansion valve, refer to page 73.
3 : In cooling, the indoor unit electronic expansion valve is used for “superheated degree control”. (Refer to page 95.)
4 : In heating, the outside unit electronic expansion valve (Y1E) is used for “superheated degree control.” (Refer to page
73.)
5 : Reference values for superheated degree to be used in the judgment of overheat operation
Suction gas superheated degree: 10°C or more Discharge gas superheated degree: 45°C or more, excluding
when it is immediately after startup, under drop control or other specific conditions.
(The values above must be used only for reference purposes. Even it is operated within the range above,operation
may be normal in other conditions.)
Referring to the Fault Tree Analysis (FTA) shown below, identify the faulty points.
Rise in
discharge
pipe
temperature
Faulty subcooling
electronic
expansion valve
(Y3E) control
Faulty
subcooling
electronic
expansion valve
Faulty
control
Faulty four-way
changeover
valve function
Faulty
discharge
pipe
temperature
control
Superheated
compressor
[In cooling]
If the indoor unit
electronic
expansion valve
excessively
throttled
(3)
Faulty
superheated
degree
control
Inadequate refrigerant
quantity
High pipe resistance
[In heating]
If the outside unit
electronic
expansion valve
excessively
throttled
(4)
Faulty control
Abnormal pipe length
Bent or Crush of pipe
Stop valve closed
(Including moisture choke)
Faulty solenoid valve coil
Faulty solenoid valve body
Faulty control PC board
Faulty valve coil
Faulty control PC board
Faulty valve body
Faulty low pressure sensor
Faulty subcooling heat
exchanger outlet thermistor
Four-way changeover valve is
located in an intermediate position
Leakage from hot gas bypass valve
Superheat caused by
axis damage
Superheat caused by
faulty compressor
Faulty valve coil
Faulty valve body
Faulty control PC board
Faulty gas pipe
thermistor of indoor unit
Faulty liquid pipe
thermistor of indoor unit
Faulty valve coil
Faulty valve body
Faulty low pressure sensor
Faulty suction pipe thermistor
Faulty control PC board
Is the connector properly connected?
Are the thermistor resistance characteristics
normal?
Is the connector properly connected?
Are the thermistor resistance characteristics
normal?
Refer to CHECK 6

Содержание

Скачать