Daikin RWEYQ26PY1 [76/342] Stopping operation

Daikin RWEYQ30PY1 [76/342] Stopping operation
Si30-813 Stop
Function 65
2. Stop
2.1 Stopping Operation
This operation is used to define the operation of the actuator while the system stops.
2.1.1 When System is in Stop Mode
Parts name Symbol
Electrical
symbol
Actuator function
Compressor (M1C) OFF
Inverter cooling fan (M1,2F) OFF
4 way valve 1 20S1 (Y5S) Holding
4 way valve 2 20S2 (Y7S) Holding
Main heat exchanger electronic exp. valve EV1 (Y1E) 0 pulse
Sub-cooling electronic exp. valve EV3 (Y3E) 0 pulse
Hot gas bypass solenoid valve SVP (Y1S) OFF
Water heat exch. oil return solenoid valve SVE (Y2S) OFF
Receiver gas charging solenoid valve SVL (Y3S) OFF
Receiver gas discharge solenoid valve SVG (Y4S) OFF
Non-operation unit liquid pipe stop solenoid valve SVSL (Y6S) ON
Ending conditions Indoor unit thermostat ON