Daikin RWEYQ26PY1 [253/342] Malfunction of system refrigerant system address undefined

Daikin RWEYQ30PY1 [253/342] Malfunction of system refrigerant system address undefined
Troubleshooting by Indication on the Remote Controller Si30-813
242 Troubleshooting
2.52
UH
Malfunction of System, Refrigerant System Address
Undefined
Remote
Controller
Display
UH
Applicable
Models
Indoor unit
FXFQ, FXCQ, FXKQ, FXDQ, FXSQ, FXMQ, FXHQ, FXAQ, FXLQ, FXNQ, FXUQ
Outside unit
RWEYQ8P, 10P
Method of
Malfunction
Detection
Detect an indoor unit with no auto address setting.
Malfunction
Decision
Conditions
The malfunction decision is made as soon as the abnormality aforementioned is detected.
Supposed
Causes
Improper connection of transmission wiring between outside unit and outside unit outside
control adaptor
Defect of indoor unit PC board
Defect of outside unit PC board (A1P)
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
NO
YES
YES
After fixing incorrect wiring,
push and hold the RESET
button on the master outside
unit PC board for 5 seconds.
Normal
NO
Is
electricity
being introduce for
the first time after
installation or after an indoor
or outside unit PC
board has been
replaced?
Is
indoor - outside and
outside - outside unit
transmission wiring
normal?
YES
Normal
NO
Does a malfunction occur?
NO
Does
a "
UH" malfunction occur
for all indoor units in
the system?
YES
NO
Does
a malfunction
occur even after 12
minutes elapses from the
time when electricity is
introduced to indoor
and outside
units?
YES
Replace indoor unit PC board.
Replace outside unit PC board
(A1P).
After fixing incorrect wiring,
push and hold the RESET
button on the outside unit
PC board for 5 seconds
Replace whichever is
defective.
The unit will not run for up to
12 minutes.