Daikin RWEYQ26PY1 [290/342] Rweyq10ptl

Daikin RWEYQ30PY1 [290/342] Rweyq10ptl
Si30-813 Wiring Diagrams
Appendix 279
RWEYQ10PTL
3D061376A
1. THIS WIRING DIAGRAM IS APPLIED ONLY TO THE OUTSIDE UNIT.
2. :FIELD WIRING.
3. :TERMINAL STRIP :CONNECTOR :TERMINAL :PROTECTIVE EARTH (SCREW)
4. WHEN USING THE OPTION ADAPTOR, REFER TO THE INSTALLATION MANUAL.
5. REFER TO THE INSTALLATION MANUAL, FOR CONNECTION WIRING TO INDOOR-OUTDOOR
TRANSMISSION F1 · F2, OUTDOOR-OUTDOOR TRANSMISSION F1 · F2, OUTDOOR-MULTI TRANSMISSION Q1 · Q2.
6.
REFER TO “SERVICE PRECAUTION” LABEL (ON EL. COMPO. BOX COVER), HOW TO USE BS1~BS5 AND DS1 SWITCH.
7. WHEN OPERATING, DO NOT SHORT CIRCUIT FOR PROTECTION DEVICE. (S1PH)
8.
BE SURE TO CONNECT THE INTERLOCK CIRCUIT (AN AUXILIARY NORMALLY OPEN CONTACT OF THE ELECTROMAGNETIC
SWITCH FOR THE HEAT SOURCE WATER PUMP) TO TERMINALS (3) AND (4) OF THE TERMINAL BLOCK (X3M).
(MAKE SURE THAT THE AUXILIARY NORMALLY OPEN CONTACT CAN SWITCH A MINIMUM LOAD OF 1 MA AT 15 VDC.)
9.
INSTALL A HEAT SOURCE WATER PUMP OPERATION CIRCUIT BETWEEN THE TERMINAL (1)-(2) OF TERMINAL STRIP (X2M),
WHEN INTERLOCKING A HEAT SOURCE WATER PUMP AND SYSTEM OPERATION.
(OPERATION POWER WILL OUTPUT FROM THE HEAT SOURCE WATER PUMP WHEN THE OPERATION DISPLAY
APPEARS ON THE INDOOR REMOTE CONTROLLER.)
10. COOL/HEAT SELECTOR CANNOT BE CONNECTED WHEN OPERATING HEAT RECOVERY SYSTEM.
11. COLORS BLK:BLACK RED:RED BLU:BLUE WHT:WHITE PNK:PINK GRY:GRAY ORG:ORANGE.
NOTES)