Daikin RWEYQ26PY1 [82/342] Normal control

Daikin RWEYQ30PY1 [82/342] Normal control
Si30-813 Normal Control
Function 71
5. Normal Control
5.1 Compressor Control
5.1.1 Compressor Control
Compressor PI Control
Carries out the compressor capacity PI control to maintain Te at constant during cooling
operation and Tc at constant during heating operation to ensure stable unit performance.
[Cooling operation]
[Heating operation]
[Cooling/Heating simultaneous operation]
Controls compressor capacity to adjust Te to achieve target value (TeS).
Te setting Te : Low pressure equivalent
saturation temperature (°C)
TeS : Target Te value
(Varies depending on Te
setting, operating frequency,
etc.)
LM (Normal)
(factory
setting)
H
3 6 7 8 9 10 11
Controls compressor capacity to adjust Tc to achieve target value (TcS).
Tc setting Tc : High pressure equivalent
saturation temperature (°C)
TcS : Target Tc value
(Varies depending on Tc setting,
operating frequency, etc.)
LM (Normal)
(factory
setting)
H
43 46 49
Controls compressor capacity to adjust Te to achieve target value (TeS) and Tc to achieve target
value (TcS) at the same time.
Te setting
LM (Normal)
(factory
setting)
H Te : Low pressure equivalent
saturation temperature (°C)
TeS : Target Te value
(Varies depending on Te
setting, operating frequency,
etc.)
3 6 7 8 9 10 11
Tc setting
LM (Normal)
(factory
setting)
H Tc : High pressure equivalent
saturation temperature (°C)
TcS : Target Tc value
(Varies depending on Tc setting,
operating frequency, etc.)
43 46 49