Daikin RWEYQ28PY1 [100/342] Outline of control indoor unit

Daikin RWEYQ30PY1 [100/342] Outline of control indoor unit
Si30-813 Outline of Control (Indoor Unit)
Function 89
9. Outline of Control (Indoor Unit)
9.1 Drain Pump Control
1. The drain pump is controlled by the ON/OFF buttons (4 button (1) - (4) given in the figure
below).
9.1.1 When the Float Switch is Tripped While the Cooling Thermostat is
ON:
1. (Normal operation):
The objective of residual operation is to completely drain any moisture adhering to the fin of the
indoor unit heat exchanger when the thermostat goes off during cooling operation.
2. (Malfunction residual):
The remote controller will display "A3" and the air conditioner will come to an abnormal stop in 5
minutes if the float switch is turned OFF while the cooling thermo is ON.
9.1.2 When the Float Switch is Tripped During Cooling OFF by
Thermostat:
*3. (Malfunction residual):
The remote controller will display "A3" and the air conditioner will come to an abnormal stop if
the float switch is turned OFF and not turned ON again within 5 minutes while the cooling
thermo is OFF.