Daikin RWEYQ28PY1 [158/342] Check operation

Daikin RWEYQ30PY1 [158/342] Check operation
Si30-813 Field Setting
Test Operation 147
3.2.8 Check Operation
To prevent any trouble in the period of installation at site, the system is provided with a test
operation mode enabling check for incorrect wiring, stop valve left in closed, coming out (or
misplacing with suction pipe thermistor) of discharge pipe thermistor and judgment of piping
length, refrigerant overcharging, and learning for the minimum opening degree of motorized valve.
Unit stopping
Press the TEST button for 5 seconds.
10 sec to 10 minutes
LED display (H1P~H7P) (
k:ON l:BLINKING h:OFF)
Pressure equalizing
Step 1
3~5 minutes
10 minutes
3 minutes
10 sec. ~ 5 minutes
Cooling start controlStep 2
Stability waiting operationStep 3
Pump down residual operation
Step 7
5 minutes
Standby for restarting
Completion
Step 8
Stop valve close check
Wrong wiring check
Refrigerant over change check
Piping length check
Judgment function
Step4~6
CHECK OPERATION FUNCTION
: Normal completion
: Abnormal completion