Daikin RWEYQ28PY1 [244/342] Troubleshooting

Daikin RWEYQ30PY1 [244/342] Troubleshooting
Si30-813 Troubleshooting by Indication on the Remote Controller
Troubleshooting 233
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
NO
Replace the outside unit PC
Board (A1P).
YES
C/H SELECT is set to "IND".
Cool / heat selection is
unified.
C/H SELECT
is set to "MASTER."
NO
C/H SELECT
is set to "SLAVE."
YES
NO
Check
and see if the following items
are normal.
NO
Does a
malfunction occur when
the cool / heat selector is
set to "IND?"
YES
Set C/H SELECT to "IND."
YES
Fix the outside units multi
connection transmission
wiring and reset power.
NO
Is the
outside units multi
connection transmission
wiring normal?
Is the
indoor / outside unit
transmission wiring
normal?
NO
YES
Fix the indior / outside unit
transmission wiring.
The cool / heat unified
address for outside units in
outside - outside unit
transmission is duplicated.
Set the address correctly.
YES
NO
NO
YES
YES
Replace the outside unit
outside control adaptor.
replacement
Replace the outside unit PC
board (A1P).
External control adaptor for outdoor unit
Is there continuity?
Does the cool/heat unified address match?
Outside unit (unified master unit)
Is there continuity?
Does the cool/heat unified address match?
Fix the problem.