Daikin RWEYQ28PY1 [57/342] Refrigerant circuit

Daikin RWEYQ30PY1 [57/342] Refrigerant circuit
Refrigerant Circuit Si30-813
46 Refrigerant Circuit
1. Refrigerant Circuit
1.1 RWEYQ8P, 10P
No. in
refrigerant
system
diagram
Symbol Name Major Function
A M1C Inverter compressor (INV)
Inverter compressor is operated on frequencies between 52 Hz and 230
Hz by using the inverter. The number of operating steps is as follows.
RWEYQ8P, 10P: 22 steps
E Y1E Electronic expansion valve (Main: EV1)
In cooling operation: High pressure control
In heating or simultaneous cooling/heating operation:
When the heat exchanger is used as the evaporator : SH control
When the heat exchanger is used as the condenser : High pressure
control
G Y3E Electronic expansion valve (Subcool: EV3)
PI control is applied to keep the outlet superheated degree of sub-
cooling heat exchanger constant.
H Y1S Solenoid valve (Hot gas: SVP)
Used to prevent the low pressure from transient falling.
IY2S
Solenoid valve (Oil return of water heat
exchanger: SVE)
Used to collect the refrigerant oil from water heat exchanger.
JY3S
Solenoid valve (Receiver gas charging:
SVL)
Used to maintain high pressure while in cooling operation at low water
temperature. And also used to prevent the accumulation of refrigerant in
non-operating outside units in the case of multiple-outside-unit system.
KY4S
Solenoid valve (Receiver gas discharging:
SVG)
Used to collect refrigerant to receiver.
M Y5S 4-way selector valve (Main: 20S1)
Changes the operation into cooling, heating or simultaneous cooling/
heating operation.
OY6S
Solenoid valve (Non-operating unit liquid
pipe closing: SVSL)
Used to prevent the accumulation of refrigerant in non-operating outside
units in the case of multiple-outside-unit system.
P Y7S 4-way selector valve (Sub: 20S2)
Changes the water heat exchanger into condenser or evaporator.
Q S1NPH High pressure sensor
Used to detect high pressure.
R S2NPL Low pressure sensor
Used to detect low pressure.
S S1PH HP pressure switch (For INV compressor)
In order to prevent the increase of high pressure when a malfunction
occurs, this switch is activated at high pressure of 4.0 MPa or more to
stop the compressor operation.
V Fusible plug
In order to prevent the increase of pressure when abnormal heating is
caused by fire or others, the fusible part of the plug is molten at a
temperature of 70 to 75°C to release the pressure into the atmosphere.
W–
Pressure regulating valve 1 (Liquid pipe to
discharge pipe)
This valve opens at a pressure of 4.0 MPa or more for prevention of
pressure increase, thus resulting in no damage of functional parts due to
the increase of pressure in transportation or storage.
2 R2T Thermistor (Suction pipe: Ts)
Used to detect suction pipe temperature, keep the suction superheated
degree constant in heating operation, and others.
3 R3T Thermistor (INV discharge pipe: Tdi)
Used to detect discharge pipe temperature, make the temperature
protection control of compressor, and others.
6 R4T Thermistor (Heat exchanger gas pipe: Tg)
Used to detect gas pipe temperature of water heat exchanger.
7R5T
Thermistor (Sub-cooling heat exchanger
outlet pipe: Tsh)
Used to detect gas pipe temperature on the evaporation side of sub-
cooling heat exchanger, keep the superheated degree at the outlet of
sub-cooling heat exchanger constant, and others.
8 R6T Thermistor (Receiver outlet liquid pipe: Tl)
Used to detect receiver outlet liquid pipe temperature, prevent the drift
between outdoor units while in heating operation in the case of multiple-
outside-unit system, and others.