Si30-813 Troubleshooting by Indication on the Remote Controller
Troubleshooting 237
2.48
UA
Indoor & Outside Units and Remote Controller
Combination Failure
Remote
Controller
Display
UA
Applicable
Models
Indoor unit
FXFQ, FXCQ, FXKQ, FXDQ, FXSQ, FXMQ, FXHQ, FXAQ, FXLQ, FXNQ, FXUQ
Outside unit
RWEYQ8P, 10P
Method of
Malfunction
Detection
Detect abnormalities in combination of indoor and outside units and the remote controller using
the outside unit PC board.
Malfunction
Decision
Conditions
When any of the followings is detected, failure is instantly confirmed.
When there is a problem in the combination of the indoor and outside units
When there is a problem in the combination of the indoor unit and the remote controller
Supposed
Causes
Excess of connected indoor units
Defect of outside unit PC board (A1P)
Mismatching of the refrigerant type of indoor and outside unit.
Setting of outside PC board was not conducted after replacing to spare parts PC board.
Troubleshooting
The number of indoor units that can be connected to a single outside unit system depends on
the type of outside unit.
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
The total
of indoor units
displaying "
UA" and
indoor units connected to the
same refrigerant system is
within connectable
number of
unit
Normal
NO
NO
There are too many indoor units
within the same refrigerant
system.
Push and hold the RESET
button on the outside unit
PC board for 5 seconds.
YES
Is the outside
PC board replaced
to spare parts PC
board ?
YES
The refrigerant classification has
not been set yet.
NO
YES
Does a malfunction occur?
Replace outside unit PC board
(A1P).
Matches the refrigerant type of
indoor and outside unit.
NO
YES
Does the
refrigerant type of indoor
and outside unit
match?