Daikin RWEYQ28PY1 [132/342] Selection of control mode no

Daikin RWEYQ30PY1 [132/342] Selection of control mode no
Si30-813 Field Setting
Test Operation 121
Selection of
Control Mode
No.
Select whether to accept or to reject the operation from the remote controller regarding the operation,
stop, temperature setting and operation mode setting, respectively, and determine the particular
control mode from the rightmost column of the table below.
(Example)
C : 3P171361-1
Operation by remote
controller (at time of
unified operation by
centralized control)
Operation by remote
controller (at time of
unified operation by
centralized control)
Operation
mode setting
by remote
controller
Temperature
control by
remote
controller
Stop by
remote
controller
[
Rejection
][
Rejection
][
Rejection
][
Acceptance
][
Acceptance
]
The control
mode is “ 1 ”.
Operation
mode
Control by remote controller
Control
mode
Operation
Stop
Temperature
control
Operation
mode setting
Unified operation,
individual operation by
central remote
controller, or operation
controlled by timer
Unified stop, individual
stop by central remote
controller, or timer stop
ON/OFF control
impossible by
remote controller
Rejection
(Example)
Rejection
(Example)
Rejection
(Example)
Rejection
Acceptance 0
Rejection 10
Acceptance
(Example)
Acceptance
(Example)
1 (Example)
Rejection 11
Only OFF control
possible by remote
controller
Acceptance
Rejection
Acceptance 2
Rejection 12
Acceptance
Acceptance 3
Rejection 13
Centralized
Acceptance
Rejection
Acceptance 4
Rejection 14
Acceptance
Acceptance 5
Rejection 15
Individual Acceptance
Rejection
Acceptance 6
Rejection 16
Acceptance
Acceptance 7
Rejection 17
Timer operation
possible by remote
controller
Acceptance
(During timer at
ON position only)
Rejection
(During timer at OFF
position)
Rejection
Acceptance 8
Rejection 18
Acceptance
Acceptance 9
Rejection 19