Daikin RWEYQ28PY1 [96/342] Pump down residual operation control

Daikin RWEYQ30PY1 [96/342] Pump down residual operation control
Si30-813 Special Operation
Function 85
7.3 Pump-down Residual Operation Control
If any liquid refrigerant remains in the heat exchanger during compressor startup, the liquid
refrigerant will enter the compressor, resulting in the dilution of the refrigerating machine oil in
the compressor and the degradation of lubricating capacity.
Therefore, before the compressor stops, pump-down operation is performed to collect the
refrigerant in the heat exchanger.
7.3.1 Cooling Operation Mode
Parts name Symbol
Electrical
symbol
Master unit operation Slave unit operation
Compressor (M1C) Current step OFF
Inverter cooling fan (M1,2F) Inverter cooling fan control Inverter cooling fan control
4 way valve (Main) 20S1 (Y5S) OFF OFF
4 way valve
(for heat exchanger)
20S2 (Y7S) OFF OFF
Main heat exchanger
electronic exp. valve
EV1 (Y1E) 2000 pulse 0 pulse
Sub-cooling electronic
exp. valve
EV3 (Y3E) 0 pls 0 pulse
Hot gas bypass solenoid
valve
SVP (Y1S) ON OFF
Water heat exch. oil return
solenoid valve
SVE (Y2S) OFF OFF
Receiver gas charging
solenoid valve
SVL (Y3S) OFF OFF
Receiver gas discharge
solenoid valve
SVG (Y4S) OFF OFF
Non-operation unit liquid
pipe stop solenoid valve
SVSL (Y6S) OFF ON
Indoor cooling unit fan (M1,2F) No instruction
Indoor cooling unit
expansion valve
EV (Y1E) All 0 pulse
Ending condition Max. 5 min.