Daikin RWEYQ28PY1 [137/342] B setting mode 2

Daikin RWEYQ30PY1 [137/342] B setting mode 2
Field Setting Si30-813
126 Test Operation
No. Setting item Description
1
Cool/heat unified
address
Sets address for cool/heat unified operation.
2 demand address Address for demand operation
4
Number of units for
sequential starting
Sets the number of units for sequential starting.
5
Indoor unit forced
fan H
Allows forced operation of indoor unit fan while unit is
stopped. (H tap)
6
Indoor unit forced
operation
Allows forced operation of indoor unit.
8 Te setting Target evaporation temperature for cooling
9 Tc setting Target condensation temperature for heating
12
External low noise
setting / Demand
setting
Reception of external low noise or demand signal
13 AIRNET address Set address for AIRNET.
20
Additional
refrigerant charge
operation setting
Carries out additional refrigerant charge operation.
21
Refrigerant
collection mode
setting
Sets to refrigerant collection mode.
26
Interlock abnormal
display setting
28
Power transistor
check mode
Check after
disconnection of
compressor wires
Used for trouble diagnosis of DC compressor. Since the
waveform of inverter is output without wiring to the
compressor, it is convenient to probe whether the trouble
comes from the compressor or PC board.
30 Demand setting 1
Changes target value of power consumption when
demand control 1 is input.
32
Normal demand
setting
Normally enables demand control 1 without external
input. (Effective to prevent a problem that circuit breaker
of small capacity is shut down due to large load.)
<Selection of setting items>
<Selection of setting conditions>
Push and hold the MODE button
(BS1) for 5 seconds and set to
“Setting mode 2”.
Push the SET button (BS2) and set
the LED display to a setting item
shown in the table on the right.
Push the RETURN button (BS3) and
decide the item. (The present setting
condition is blinked.)
Push the SET button (BS2) and set
to the setting condition you want.
Push the RETURN button (BS3) and
decide the condition.
Push the RETURN button (BS3) and
set to the initial status of “Setting
mode 2”.
If you become unsure of how to
proceed, push the MODE button
(BS1) and return to setting mode 1.
b. “Setting mode 2”