Daikin RWEYQ28PY1 [243/342] Malfunction of transmission between outside units

Daikin RWEYQ30PY1 [243/342] Malfunction of transmission between outside units
Troubleshooting by Indication on the Remote Controller Si30-813
232 Troubleshooting
2.45
U7
Malfunction of Transmission between Outside Units
Remote
Controller
Display
U7
Applicable
Models
Outside unit
RWEYQ8P, 10P
Method of
Malfunction
Detection
Microcomputer checks if transmission between indoor unit and remote controller is normal.
Malfunction
Decision
Conditions
When transmission is not carried out normally for a certain amount of time
Supposed
Causes
Improper connection of transmission wiring between outside unit and external control
adaptor for outdoor unit.
Improper cool/heat selection
Improper cool/heat unified address (outside unit, external control adaptor for outdoor unit)
Defect of outside unit PC board (A1P)
Defect of external control adaptor for outdoor unit
Improper connection of transmission wiring between outside units of multi outside unit
connection.