Daikin RWEYQ28PY1 [146/342] Multi outside units connection

Daikin RWEYQ30PY1 [146/342] Multi outside units connection
Si30-813 Field Setting
Test Operation 135
e Set Cool / Heat for More Than One Outside Unit System Simultaneously in Accordance with Unified
Master Outside Unit by Indoor Unit Remote Controller
Install the outside unit external control adaptor on either the outside unit-outside unit, indoor-
outside, or transmission line.
Set outside unit PC board DS1-1 to “Indoor” (factory set).
In setting mode 1, set the outside unit you want to give cool/heat selection permission to as
the group master, and set the other outside units as group slave units.
Set the outside unit external control adaptor SS1 to Unified (factory set) or Cool, and SS2 to
No (factory set).
Multi outside units connection